The Pensky Marten flash point apparatus finds the lowest temperature at which a fuel or oil gives off enough vapour to ignite briefly in a closed cup. We manufacture it in India with a full fuel testing range. This page lists model codes for refineries, depots, power stations and colleges in Côte d'Ivoire, Cameroon, Mozambique, DR Congo and Botswana.

Our Pensky Marten flash point apparatus and fuel range

These products are from our Fuel Testing Lab Equipment category.

ProductModel codeProperty measured
Pensky Marten Flash and Fire Point ApparatusFTE-0006Flash and fire point in a closed cup
Abels Flash Point ApparatusFTE-0003Flash point of low flash point products
Cleveland Flash Point ApparatusFTE-0008Flash and fire point in an open cup
Redwood ViscometerFTE-0002Viscosity by flow time
Bomb CalorimeterFTE-0007Calorific value of solid and liquid fuels
Cloud and Pour Point ApparatusFTE-0014Low-temperature behaviour
Carbon Residue Test ApparatusFTE-0015Carbon residue
Fuel Distillation ApparatusFTE-0018Boiling range
Junkers Gas CalorimeterFTE-0016Calorific value of gaseous fuels
Melting Point ApparatusFTE-0012Melting point apparatus

Choosing the flash point method

MethodCupTypical products
Pensky-MartensClosed, stirredDiesel, fuel oil, lubricating oil, biodiesel
AbelClosedKerosene and other low flash point products
ClevelandOpenLubricating oils, bitumen

Closed cup results are lower than open cup results for the same sample, because vapour cannot escape. Specifications name the method, so check before ordering.

Applications

  • Checking diesel and kerosene at depots for contamination with petrol.
  • Classifying products for safe storage and transport.
  • Monitoring lubricating and transformer oils in service.
  • Teaching fuels and combustion in a mechanical engineering lab.

Features

  • Made to IS, BS, EN, ASTM or AASHTO as applicable. Name the method number in your enquiry.
  • Test cup, lid, stirrer and shutter supplied as a set.
  • Electric heating with regulator.
  • Thermometers quoted to the range of the method.

Automation level and heater ratings depend on the model. We confirm them in the quotation.

Running a fuel laboratory safely

Flash point tests involve heated flammable liquids. Work under extraction, keep sample sizes small, and have a suitable extinguisher at hand. Store samples in closed containers away from the test bench. Use a reference material with a known flash point to check the apparatus at the interval your method sets. Barometric pressure affects the result, so record it and apply the correction in the standard.

Sampling comes first

A flash point result is only as good as the sample. Light fractions escape quickly, so fill containers nearly full, close them tightly and keep them cool until the test. Do not transfer samples between containers more than necessary, and never store them in plastic that fuel can permeate. Label each one with source, date and time, so that a failing result can be traced back to a tank or delivery.

Markets served: import and site notes

CountryNominal mains supplyUsual port of entryNote for this equipment
Côte d'Ivoire220 V, 50 HzAbidjanThe refinery and coastal depots test every delivery. Flash point is a first-line check.
Cameroon220 V, 50 HzDoualaFuel moves long distances by road, raising adulteration risk. Portable checks at depots help.
Mozambique220 V, 50 HzMaputo, Beira or NacalaPort fuel terminals serve inland neighbours. Each needs a small quality lab.
DR Congo220 V, 50 HzMatadi (west); Dar es Salaam route for the east and southMining fleets burn large diesel volumes. Site labs check fuel on receipt.
Botswana230 V, 50 HzDurban or Walvis Bay, then road (landlocked)All fuel is imported. Border and depot labs confirm product grade.

Why buy from us

  • Manufacturer of the full fuel test equipment set.
  • Related energy equipment such as engine test benches on the same order.
  • Model codes for tender lists.
  • Installation and training offered.

How to order

  1. List the properties and method numbers.
  2. State sample types and numbers per day.
  3. Give voltage and destination.
  4. We send a quotation.

Send your requirement through the contact page. Fuel testers are priced per method and configuration.

Frequently asked questions

Do you supply a digital bomb calorimeter?

A Bomb Calorimeter is listed. Tell us if you need a digital readout and we will confirm the version.

Is this suitable as transformer oil testing equipment?

Flash point and viscosity are part of transformer oil testing. Electrical tests such as breakdown voltage need separate equipment, so ask us about those.

Is the melting point determination apparatus for fuels?

It is used for waxes and solid products. It sits in the same category.